 |
Telecommunications Room
The Telecommunications Room:
- is the cross connect location for the horizontal and backbone cabling
- shall be able to contain telecommunications equipment, terminations and related wiring
- shall be located as close as possible to the center of the area served
- shall be the termination point for horizontal pathways for the area being served
- shall be seismic rated where applicable
Design
The telecommunications room:
- shall be dedicated to telecommunications related functions and should not be shared with electrical facilities
- shall not have duct work not associated to the telecommunications system pass through or enter the telecommunications room
- shall be interconnected with another telecommunications room on the same floor by a conduit (trade size 3), or equal.
Size and Spacing
There shall be one telecommunications room per floor except when:
- the floor area served is greater than 1000m2
- the horizontal distance is greater than 90m
- Add one Telecommunications Room for every of 1000m2 floor area.
Floor Loading
Telecommunications rooms shall be located on floor areas designed with a minimum floor loading of 2.4 kPa (50 Ibf/ft 2)
Provisioning
Telecommunications Rooms shall:
- have a minimum of two walls should be covered with 20mm (3/4 in) plywood, preferably void free, 2440mm (8 ft) high, capable of supporting attached equipment. Plywood should be either fire-rated or covered with two coats of fire retardant paint
- have lighting that is minimum of 500 Ix (50 foot candles) measured 1 m (3 ft ) above the finished floor, mounted 2600 mm (8.5 ft) minimum above finished floor and should not be powered by the same circuit as the telecommunications equipment. Dimmer switches shall not be used
- not have a false ceiling
- have a door which is 910mm (36”) wide and 2000mm (80”) high without a door sill. It shall open outward, side to side or be removable and lockable.
- have floors and ceilings treated to eliminate dust
- have 2 dedicated 120V, 20 AMP, non switched, ac duplex outlets located at 6ft intervals around the perimeter wall at a height of 150 mm (6”) above the floor
- have access to the telecommunications grounding system
- should have pulling sleeves and slots located next to the doorway (see 5.2.2.2 of the original standards documentation)
- have fire protection equipment as per local codes
- have sprinkler heads with wire cages
- have HVAC in its design to maintain a temperature equal to that of the adjacent offices.
I would like to thank " cablingdB.com" for relevant information regarding the USA and Canadian Standards. Please visit their site for more information regarding the American Structured Cabling Standards.
|
 |